Accurate modeling of cables is important to study the behavior of high frequency disturbances in power converter systems. This paper reviews and compares two popular methodologies to model energy cables – an improved per unit length parameters based model and a Laplace SPICE element based model. The two models presented take into account the frequency dependence of the parameters of the cable. A ladder network is used for this purpose in the per unit length based model. The Laplace SPICE element model is generated from from a rational function approximation for the admittance parameters that are frequency dependant. The rational function approximation is obtained using a well known vector fitting algorithm. The time and frequency domain solutions of a two wire energy cable, obtained from the two models, agree well.
Available at: http://works.bepress.com/uma-balaji/22/
Copyright © 2018 Institute of Advanced Engineering and Science. All rights reserved