Skip to main content
Article
Thermal Mixing of Outdoor and Return Airflows in Typical Air-Handling Units
ASHRAE Transactions
  • Milind S. Mainkar
  • Fathi Finaish, Missouri University of Science and Technology
  • Robert Van Becelaere
  • Harry J. Sauer, Jr., Missouri University of Science and Technology
Abstract

This paper examines thermal mixing of outdoor and return air streams in typical air-handling units equipped with parallel blade dampers. The mixing of the two air streams in rectangular and square mixing chambers is studied for eight different dampers and blade orientations. Testing is conducted at a total supply air of 16000 CFM with outdoor flow percentages of 15% and 30%. The temperature differential between the outdoor and return airflows is kept at 40°F Damper blades with chords of 4 and 6 inches are tested. To examine the mixing of the two air streams, temperature distributions in the mixed region are measured by an array of thermocouples and utilized to compute the thermal mixing effectiveness of the mixed flow. It appears that the relative flow momentum of the two streams plays an important role in the mixing Values of range mixing effectiveness increase significantly with increase in the return air velocity However, this conclusion is not applicable to configurations with minimum outside air in which cold spots can occur downstream in the mixing box. Retesting of configurations producing the least stratification at 50% total supply airflow shows that thermal mixing is degraded, particularly for the cases of 15% outside air.

Department(s)
Mechanical and Aerospace Engineering
Sponsor(s)
American Society of Heating, Refrigerating and Air-Conditioning Engineers
Keywords and Phrases
  • Thermal Properties,
  • Thermoelectric Apparatus and Appliances,
  • Aerodynamics,
  • Air,
  • Blades,
  • Speed,
  • Temperature
Document Type
Article - Journal
Document Version
Citation
File Type
text
Language(s)
English
Rights
© 2004 American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE), All rights reserved.
Publication Date
1-1-2004
Publication Date
01 Jan 2004
Citation Information
Milind S. Mainkar, Fathi Finaish, Robert Van Becelaere and Harry J. Sauer. "Thermal Mixing of Outdoor and Return Airflows in Typical Air-Handling Units" ASHRAE Transactions (2004)
Available at: http://works.bepress.com/fathi-finaish/29/